Sec. 9-9-27. Appendix B—Fire-flow requirements for buildings.

Appendix B Section B105.2 is amended to read as follows:
B105.2 Buildings other than one- and two-family dwellings. The minimum fire-flow and flow duration for buildings other than one- and two-family dwellings shall be as specified in Table B105.1.
Exception: A reduction in required fire-flow of up to 50 percent, as approved by the fire code official, is allowed when the building is provided with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1. The resulting fire-flow shall not be less than 1500-gallons per minute for the prescribed duration as specified in Table B105.1.
(Ord. No. 1489, § 5 (part).)